Fluke 117
The Fluke 117 Electricians Multimeter is a compact, CAT III 600 V, True-rms meter that includes an easy-to-use interface with a bright backlight for darker worksites. It saves you time and enables you to move from job to job more quickly. With a quick turn of the dial you can get measurements for:
For the everyday
A digital multimeter designed to be hauled everywhere with you, part of your everyday tools. The 117 is built for demanding applications like:
Non-contact voltage detection
Keep yourself safer with integrated VoltAlert™ technology. Fast, go/no go non-contact voltage detection built into your multimeter saves you from having to carry around or find an extra tool to get the work started.
Automatic AC/DC selection
Set the dial and get your measurement quickly with AutoVolt. This automatic AC/DC voltage selector makes it easier for you to get the measurement you need and move on quicker.
Frequently asked questions
What is the difference between the Fluke 115 and the Fluke 117?
While similar, the Fluke 115 and the Fluke 117 meters are designed for slightly different purposes. The Fluke 115 is a compact true-rms digital multimeter that’s great for field service. The Fluke 117 is a designed specifically for electricians. With a quick turn of the dial both units provide measurements for:
The Fluke 117 offers non-contact voltage detection and has a selectable low-impedance mode to prevent false readings from ghost voltage. The 117 also features automatic selection of AC or DC voltage, depending on what was detected.
Maximum voltage between any terminal and earth ground |
600 V |
|
Safety |
IEC 61010-1: Pollution Degree 2 |
|
Fuse for A input |
11 A, 1000 V FAST Fuse (Fluke PN 803293) |
|
Display |
Digital: 6,000 counts, updates 4 per second |
|
Bar graph |
33 segments, updates 32 per second |
|
Operating temperature |
-10°C to +50°C |
|
Storage temperature |
-40°C to +60°C |
|
Battery type |
9 volt Alkaline, IEC 6LR61 |
|
Battery life |
400 hours typical, without backlight |
|
Accuracy Specifications |
||
DC millivolts |
Range/resolution |
600.0 mV / 0.1 mV |
Accuracy |
±([% of reading] + [counts]): 0.5% + 2 |
|
DC volts |
Range/resolution |
6.000 V / 0.001 V |
Accuracy |
±([% of reading] + [counts]): 0.5% + 2 |
|
Auto volts |
Range/resolution |
600.0 V / 0.1 V |
Accuracy |
2.0% + 3 (DC, 45 Hz to 500 Hz) |
|
AC millivolts¹ True RMS |
Range/resolution |
600.0 mV / 0.1 mV |
Accuracy |
1.0% + 3 (DC, 45 Hz to 500 Hz) |
|
AC volts¹ True RMS |
Range/resolution |
6.000 V / 0.001 V |
Accuracy |
1.0% + 3 (DC, 45 Hz to 500 Hz) |
|
Continuity |
Range/resolution |
600 Ω / 1 Ω |
Accuracy |
Beeper on < 20 Ω, off > 250 Ω detects opens or shorts of |
|
Ohms |
Range/resolution |
600.0 Ω / 0.1 Ω |
Accuracy |
0.9% + 1 |
|
Range/resolution |
40.00 MΩ / 0.01 MΩ |
|
Accuracy |
5% + 2 |
|
Diode test |
Range/resolution |
2.00 V / 0.001 V |
Accuracy |
0.9% + 2 |
|
Capacitance |
Range/resolution |
1000 nF / 1 nF |
Accuracy |
1.9% + 2 |
|
Range/resolution |
> 1000 μF |
|
Accuracy |
5% + 20% |
|
Lo-Z capacitance |
Range |
1 nF to 500 μF |
Accuracy |
10% + 2 typical |
|
AC amps True RMS (45 Hz to 500 Hz) |
Range/resolution |
6.000 A / 0.001 A |
Accuracy |
1.5% + 3 |
|
DC amps |
Range/resolution |
6.000 A / 0.001 A 10.00 A / 0.01 A |
Accuracy |
1.0% + 3 |
|
Hz (V or A input)² |
Range/resolution |
99.99 Hz / 0.01 Hz |
Accuracy |
0.1% + 2 |